Access is required to drainage installations for testing, inspection and removal of debris. Access to drainage allowing rodding in both directions can be provided by inspection chambers. Rodding eyes provide access for clearance of debris in the direction of flow only and should only be used in conjunction with an access chamber or manhole at a point downstream.

No part of the drain should be more than 50 metres away from a manhole. The distance between points should therefore not exceed 100 metres.

Generally speaking, access should be provided at all changes in direction, gradient or pipe size, unless rods can pass through unimpeded.

Where a junction between two drains does not have a manhole, access should be provided within 12 metres of the junction.

*

Note: If you are installing a new soil stack or drainage system, or significantly altering an existing system, you will need to inform the Building Control Department at your local Council. You will need to demonstrate that the work carried out conforms to Building Regulations: England & Wales or Scotland

*
-
*