You are here: Home > Self Builder > Soil & Waste > Design > Soil Stack Design

Product Selector
*

Soil Stack Design

Soil Stack Design

Soil stack design

L = 450mm, up to three storeys high
L = 740mm, up to five storeys high
L = one storeyheight, over five storeys 

Bends at the base of stacks should be of long radius. Two 45° bends may be used as an alternative. The same principle should be used for offsets.

*
Soil stack design

The distance between the centre line of the lowest branch connection and the invert of the drain should be at least 450mm. 

*

Stub stacks

Stub stacks

A group of ground floor appliances may be connected to drain using an unventilated stub stack. The vertical drop to the invert level of the drain must not exceed 1.5m from a WC and 2.5m from a waste appliance.

*
-
*